ETTV တြက္နည္း ( Heat Load Calculation )

ပထမဆံုးအခ်က္ေနၿဖင့္ ETTV Formula သည္ နုိင္ငံကိုလုိက္၍ေၿပာင္းလဲသည္။
ဒုတိယ Assumptions မ်ားၿပဳလုပ္ထားသည္။
ETTV Value တြက္နည္း တြင္ ေအာက္ပါတ့ိုကို Assumption လုပ္ထားသည္။
က) Building Envelope is fully enclosed. အေဆာက္အဦးတစ္ခုလံုးသည္ နံရံမ်ားၿဖင့္ လြတ္သည့္ေနရာမရွိေအာင္ကာရံထားသည္ဟုယူဆထားသည္။
ခ) Convention Heat Trasfer through building Enveloped opening portion is ignored.
အေဆာက္အဦး၏ တံခါးမ်ား၊ ဝင္ေပါက္ထြက္ေပါက္မ်ားမွ Convention နည္းၿဖင့္ အပူမ်ားစီးဝင္ၿခင္း (Air Conditioning အတြက္) ႏွင့္ အပူမ်ားစီးထြက္ၿခင္း(Heating System အတြက္) ကို ထည့္သြင္းတြက္ခ်က္ၿခင္းမၿပဳလုပ္ပါ။
ETTV ပံုေသနည္း

ETTV တန္ဘုိးသည္ တြင္ အပိုင္း၃ခုပါဝင္သည္။
1) Heat conduction Through Opaque Walls အပိုင္း
Heat conduction Through Opaque Walls = 12(1-WWR) Uw
Constant number 12 သည္ အၿပင္အပူခ်ိန္ (35C - 23C = 12C) ၿဖစ္သည္။
အေဆာက္အဦး အတြင္း ႏွင့္ အၿပင္တြင္ အပူခ်ိန္ကြာၿခားသည့္အခါ ၿမင့္သည့္အပူခ်ိန္ T1 မွ နိမ့္သည္အပူခ်ိန္ T2 သို့ နံရံမ်ား ကို ၿဖစ္၍ အပူစီးကူးမွဳၿဖစ္ေပၚသည္။ ဥပမာ ၿပင္ပအပူခ်ိန္ 35C မွ အေဆာက္အဦး အတြင္း အပူခ်ိန္ 23C သို့ conduction အပူစီးကူးမွဳၿဖစ္ေပၚသည္။
WWR သည္ window to wall ratio ၿဖစ္သည္။ နံရံတစ္ဘက္၏ ဧရိယာတစ္ခုလံုးကို ကိန္းၿပည့္ဂဏန္း ၁ အၿဖစ္ယူၿပီး WWR သည္ နံရံတစ္ခုလံုးတြင္ Window ဧရိယာရာခုိင္နွဳန္းမည္မွ်ၿဖစ္သည္ကို ဆုိလုိသည္။
WWR = 0.6 ဆုိသည္မွာ နံရံတစ္ဘက္တြင္ ဧရိယာတစ္ခုလံုး၏ ၆၀% သည္ window မ်ားၿဖစ္သည္ ဟုဆုိလိုသည္။ က်န္၄၀ ရာခုိင္ႏွဳန္းမွာ fenesate နံရံမ်ားၿဖစ္သည္။
Uw သည္ နံရံအမ်ိဳးအစားႏွင့္သက္ဆုိင္ေသာ U တန္ဘုိးၿဖစ္သည္။
Heat (Q) = U x Area x Dfferential Temperature မွ simplified လုပ္ထားသည္ Formula ၿဖစ္သည္။
ဥပမာ
အေဆာက္အဦးတစ္ခု၏အေရ့ွဘက္သုိ့မ်က္ႏွာမူေသာနံရံတစ္တစ္ခု၏ဧရိယာသည္ စတုရန္းမီတာ ၁၀၀ ၿဖစ္ၿပီး ဧရိယာ၏၅၀%သည္ ၿပဳတင္းေပါက္မ်ားၿဖစ္လွ်င္ ထုိနံရံ၏ ၿဖစ္ေပၚေသာ Heat Conduction ကို ရွာပါ။ ေအာက္တြင္ၿပထားေသာ U တန္ဘုိး 0.3 W/m2 K ၿဖစ္သည္။
အထက္တြင္ေဖာ္ၿပထားေသာ ETTV ၏ စင္ကာပူတြင္ အသံုးၿပဳရန္အတြက္သတ္မွတ္ထားေသာ ပံုေသနည္းအရ အတြင္းႏွင့္အၿပင္ အပူခ်ိန္ၿခားနားခ်က္သည္ ၁၂ ဒီဂရီC ၿဖစ္သည္။
Heat conduction Through Opaque Walls = 12(1-WWR) Uw = 12 (1-0.5) 0.3 =1.8 W per Sq meter ၿဖစ္သည္။
အဓိပၸါယ္မွာ အေရ့ွဘက္သုိ့မ်က္ႏွာမူေသာနံရံ၏ ၁ စတုရန္းမီတာ တုိင္းမွ အပူပမာဏ 1.8 Watt စီးကူးဝင္ေရာက္လာမည္ဟုဆုိလုိသည္။
U တန္ဘိုးကို ASHRE Hand Book မ်ား။ Singapore BCA ၏ Data မ်ား ႏွင့္ ထုပ္လုပ္သူမ်ားထံမွ ရရွိနုိင္သည္။
U တန္ဘိုး အနည္းအမ်ားသည္ ေအာက္ပါ အခ်က္အလက္မ်ားေပၚတြင္မူတည္သည္။
Envelope Layers of Materials
Thickness of Material
Thermal Conductivity of Materials (K Value or R Value)
Air Resistance
Thermal Conductivity (K Value)
K တန္ဘုိးသည္နံရံ အမ်ိဳးအစားကို လုိက္၍ အေဆာက္အဦးတြင္းသုိ့ အပူစီးကူနုိင္စြမ္း (ablility of a material to trasmit heat) ကိုဆုိလိုသည္။
အတြင္းနံရံႏွင့္ အၿပင္နံရံအၾကားတြင္ unit temperature difference ၿဖစ္ေပၚသည့္ steady-state conditions တြင္ unit area of the material of unit thickness မွ trasmit လုပ္ေသာအပူ(Heat) ပမာဏသည္ K တန္ဘုိး ၿဖစ္သည္။
Quantitiy of heat trasmiteed under steady-state conditions through unit area of the material of unit thickness in unit time when unit temperature difference exists between its opposite surface (W/m K)
ကြန္ကရစ္နံရံ ၏ K တန္ဘုိးသည1.44 watt ၿဖစ္သည္။ အဓိပၸါယ္မွာ ၁ မီတာအထူ ကြန္ကရစ္နံရံမွ ၁ ဒီဂရီK အပူခ်ိန္ကြာၿခားမွဳေၾကာင့္ trasmit လုပ္ေသာအပူ(Heat) ပမာဏသည္ 1.44 watt ၿဖစ္သည္။
the lower the better. K တန္ဘုိးသည္ နည္းေလ အေဆာက္အဦးတြင္းသုိ့ အပူစီးကူမွဳနည္းေလၿဖစ္သည္။
2) Heat conduction Through Glass Windows အပိုင္း
Heat conduction Through Glass Windows = 3.4 (WWR) Uf
Heat (Q) = U x Area x Dfferential Temperature မွ simplified လုပ္ထားသည္ Formula ၿဖစ္သည္။
Dfferential Temperature = 3.4 C ၿဖစ္သည္။
Area မွာ Window မ်ားအားလံုး၏ စုစုေပါင္းဧရိယာ ၿဖစ္သည္။ Window Schedule ကို Architech ထံမွ ရရွိနုိင္သည္။  

Solar Radiation Though Glass Windows = 211 (WWR) (CF) (SC)
Mean Solar Radiation = 112 Watt per Sq meter
Solar Radiation ဆုိသည္မွာ ေန သည္ ကမၻာေၿမမွ မုိင္းေပါင္းမ်ားစြာကြာေဝးေသာေၾကာင့္ေနေရာင္ၿခည္သည္ ကမၻာေၿမေပၚသိုေရာက္ရွိခ်ိန္တြင္ ေနေရာင္ၿခည္ Paralley Sun's Rays မ်ားၿဖစ္သို့ေရာက္ရွိသြားသည္။ ေနေရာင္ၿခည္ Heat Energy ႏွင့္ Light Energy ကို လူသားတုိ့အတြက္သယ္ေဆာင္လာသည္။ အထူးသၿဖင့္ ေနေရာင္ၿခည္ မွ သယ္ေဆာင္လာေသာ Heat Energy ကို Solar Radiation ဟုေခၚဆုိၾကသည္။
The solar factor has been derived from the annual average of solar radiation transmitted through a 3mm clear glass window.
မိမိအေဆာက္အဦးတည္ရွိရာေနရာ Latitude and Longitude ကိုလုိက္၍ Solar Radiation ပမာဏ ကြာၿခားမွဳရွိသည္။ လ(month) ကို လုိက္၍လည္း Solar Radiation ပမာဏကြာၿခားမွဳရွိသည္။ Orientation ကို လုိက္၍လည္း Solar Radiation ပမာဏကြာၿခားမွဳရွိသည္။ စင္ကာပူအတြက္ တစ္နွစ္တာ ပွ်မ္းမွ် Solar Radiation မွာ 211 Watt per sq meter ၿဖစ္သည္။ အဓိပါၸယ္မွာ ေနေရာင္ၿခည္မွ တစ္စတုရန္းမီတာေပၚတြင္ တစ္နွစ္တာပွ်မ္းမွ် Solar Radiation (Radiation အပူ) ၏ ပမာဏ မွာ 211 Watt per sq meter ၿဖစ္သည္။
SC = SC ×SC
where
SC : shading coefficient of the fenestration system
SC1 : shading coefficient of glass or effective shading coefficient of
glass with solar control film where a solar control film is used on the glass
SC2 : effective shading coefficient of external shading devices
ေအာက္ပါဇယားသည္ Solar Correction Factor (CF) for Wall ၿဖစ္သည္။
တၿခားေသာ Orientation ႏွင့္ တၿခားေသာ Pitch Angles မ်ားအတြက္ correction factor ကို interpolation နည္းၿဖင့္တြက္ယူနုိင္ပါသည္။
Pitch Angles ကိုေအာက္ပါ အေဆာက္အဦးနွစ္ခုၿဖင့္ရွင္းၿပနုိင္ပါသည္။
Wheelock Place Building Pitch Angles is below 90 Degree
Most of building Pitch Angles are 90 Degree Concourse Building Pitch Angles is above 90 Degree

1 comment: